Representative photo. Please check item description for details.

APD 4003 Series Potentiometer Input to DC Transmitter, Isolated, Factory Ranged, DIN Rail Mount

https://www.branom.com/web/image/product.template/534048/image_1920?unique=2efc457
(0 review)

Manufacturer: Absolute Process Instruments Aka Api

Mfg Product Code: APD4003

Weight: 5.0 lb(s)

On Hand: 0

The APD 4003 accepts a resistance input from potentiometer, slidewire, linear position, displacement, or rotational devices and provides an optically isolated DC voltage or current output that is linearly related to the potentiometer position.

The APD 4003 will accept any potentiometer with a value of 0-100 Ω through 0-1 MΩ without recalibration and without affecting accuracy. The APD 4003 output is factory ranged. Consult factory for offsets and/or input ranges other than 0 to 100% of the potentiometer range or see the APD 4008.

The full 3-way (input, output, power) isolation makes this module useful for ground loop elimination, common mode signal rejection, and noise pickup reduction.

Features:

  • Accepts Most Full-Range Potentiometers

  • Factory Ranged Voltage or Current Output

  • Removable Plugs for Faster Installation

  • Full 1200 V Input/Output/Power Isolation

  • Input and Output LoopTracker® LEDs

  • Functional Output Test Button

  • Selectable Sink/Source for Current Output

389.00 389.0 USD 389.00

389.00

Not Available For Sale

  • Power
  • Input
  • DC Output Range
  • Optional Fast Response
  • Optional Input/Output Reversal
  • Optional Moisture Resistance

This combination does not exist.


Product Datasheets

Datasheet 1

APD 4003 Series Potentiometer Input to DC Transmitter, Isolated, Factory Ranged, DIN Rail Mount

  • Power
  • Input
  • DC Output Range
  • Optional Fast Response
  • Optional Input/Output Reversal
  • Optional Moisture Resistance

389.00 389.0 USD 389.00

389.00

Not Available For Sale

This combination does not exist.


Input:Any Full-Range Potentiometer up to 1 MegaOhm


Specifications

Power 85-265 VAC, 60-300 VDC or [D] 9-30 VDC, 10-32 VAC
DC Output Range Voltage: 0-1 VDC to 0-10 VDC, 10 mA max or [M09] Voltage M09: 0-10 VDC to 0-20 VDC or Bipolar Voltage: ±50 mVDC to ±10 VDC or Current: 0-2 mADC to 0-20 mADC
Optional Fast Response Without or [DF] Fast Response
Optional Input/Output Reversal Without or [R] I/O Reversal
Optional Moisture Resistance Without or [U] Conformal Coating
Input Any Full-Range Potentiometer up to 1 MegaOhm